RII-E101
Division 06 — Electrical Insulation Mats
Electrical Insulation Mats — IS 15652 / IEC 61111
Elastomer insulating mats in Class A/B/C, routine tested for dielectric strength, for personnel protection around live equipment.
SEC / 01–02
Features & Applications
Key Features
- Certified to IS 15652 : 2006 and IEC 61111
- Class A (3.3 kV), B (11 kV), C (33 kV) grades
- Fire-retardant, anti-skid top surface
- Resistant to oil, acid and low temperature
- Each roll marked and test certified
Typical Applications
- HT/LT switchboard and panel rooms
- Substations and control rooms
- Generator and transformer bays
- Lift machine rooms
- Industrial electrical installations
SEC / 03
Technical Specifications
| Standards | IS 15652 : 2006 / IEC 61111 |
|---|---|
| Classes | A (3.3 kV) / B (11 kV) / C (33 kV) |
| Proof voltage | 10 / 22 / 36 kV respectively |
| Thickness | 2.0 / 2.5 / 3.0 mm |
| Roll size | 1 m / 2 m × 10 m |
| Surface | Fine-ribbed / checkered anti-skid |
| Supply form | Rolls with test certificate |
Values above are indicative of standard grades. Confirm final specification against your service conditions with our team before ordering.